AC120-2
Cytech
Telecom, Battery, Integrated
IP 55, IP 65
Half-embeded Mount, Door Mount
2000W/6800BTU
| Availability: | |
|---|---|
Product Description
The AC2000W enclosure air conditioning utilizes a closed-loop refrigeration system to provide consistent cooling for lithium battery cabinets, preventing heat accumulation that can degrade battery performance.
Designed for indoor and outdoor lithium battery storage environments, the system combines efficiency, low noise operation, and durability. Its enclosure air conditioning for lithium battery cabinet configuration ensures maximum safety, minimizing the risk of overheating or condensation.
Compact, durable design suitable for lithium battery cabinets
Closed-loop cooling to prevent dust, moisture, and contamination
LED digital display with precise temperature control
RS485 / Modbus-RTU interface for remote monitoring
Over-temperature alarm and fault protection
Optional heater for low-temperature environments
Corrosion-resistant enclosure for industrial and outdoor use
Self-diagnosis and real-time system monitoring
Easy installation: side-mount or door-mount
Name | Enclosure Air Conditioneing AC 2000 W |
Model | AC120-2 |
Main power supply | 220VAC±15% 50Hz/60Hz |
Cooling capacity(Rated) | 2000W@L35/L35 |
Power consumption(Rated) | 780W@L35/L35 |
Heating capacity(optional) | 1000W |
Air flow | 500m3/h |
Cooling current (rated/Max.) | 14.8A/19.0A |
Work temp. range | -40℃~+55℃ |
Noise | 63dB(A) |
IP Grade | IP55,NEMA 4,NEMA 4X |
Net Weight | 33KG |
Refrigerant | R134a |
Note:@L35/L35 is Internal temperature 35℃, ambient temperature 35℃
Enclosure air conditioning for lithium battery cabinet Cooling Princple : the high-pressure refrigerant liquid in the system enters the evaporator and evaporates to absorb heat of the air in the cabinet, so the air is cooled, and the refrigerant that evaporates into gas in the evaporator is inhaled by the compressor and compressed into the high-pressure and high-temperature refrigerant gas, which enters the condenser and cooled to refrigerant liquid, and then re-enters the evaporator to cool the indoor air, and circulates accordingly.

Application
The AC2000W enclosure air conditioning for lithium battery cabinet is ideal for:
Indoor and outdoor lithium battery storage cabinets
Modular battery systems and BESS (Battery Energy Storage Systems)
Power conversion system (PCS) enclosures
Battery inverter and control cabinets
Industrial energy storage installations
Options
Model | Voltage | Nominal cooling capacity(W) (L35/L35) | Nominal cooling capacity(Btu/hr) (L35/L35) | Power consumption(W)(L35/L35) | IP Grade | Heater (W)(option) | Internal air flow (m3/h) | Refrigerant | Noise (dbA) |
220VAC 50Hz | 300 | 1020 | 170 | IP55,NEMA 4, NEMA 4X | 500 | 100 | R134a | 56 | |
220VAC 50Hz | 400 | 1360 | 215 | IP55,NEMA 4, NEMA 4X | 500 | 110 | R134a | 56 | |
220VAC 50Hz | 500 | 1700 | 280 | IP55,NEMA 4, NEMA 4X | 500 | 120 | R134a | 56 | |
220VAC 50Hz | 1000 | 3400 | 430 | IP55,NEMA 4, NEMA 4X | 1000 | 230 | R134a | 62 | |
220VAC 50Hz | 1200 | 4080 | 498 | IP55,NEMA 4, NEMA 4X | 1000 | 240 | R134a | 62 | |
220VAC 50Hz | 1300 | 4440 | 532 | IP55,NEMA 4, NEMA 4X | 1000 | 260 | R134a | 63 | |
220VAC 50Hz | 1500 | 5100 | 600 | IP55,NEMA 4, NEMA 4X | 1000 | 300 | R134a | 63 | |
CYAC120-2 | 220VAC 50Hz | 2000 | 6800 | 745 | IP55,NEMA 4, NEMA 4X | 1000 | 500 | R134a | 63 |
220VAC 50Hz | 2500 | 8500 | 846 | IP55,NEMA 4, NEMA 4X | 2000 | 560 | R134a | 63 | |
220VAC 50Hz | 3000 | 10200 | 1240 | IP55,NEMA 4, NEMA 4X | 2000 | 720 | R134a | 63 | |
220VAC 50Hz | 3500 | 11900 | 1360 | IP55,NEMA 4, NEMA 4X | 2000 | 1250 | R134a | 63 | |
220VAC 50Hz | 5000 | 17000 | 2000 | IP55,NEMA 4, NEMA 4X | 2000 | 2300 | R134a | 63 |
Model | Voltage | Nominal cooling capacity(W) (L35/L35) | Nominal cooling capacity(Btu/hr) (L35/L35) | Power consumption(W)(L35/L35) | IP Grade | Heater (W)(option) | Internal air flow (m3/h) | Refrigerant | Noise (dbA) |
220VAC 60Hz | 300 | 1020 | 170 | IP55,NEMA 4, NEMA 4X | 500 | 100 | R134a | 56 | |
220VAC 60Hz | 400 | 1360 | 215 | IP55,NEMA 4, NEMA 4X | 500 | 110 | R134a | 56 | |
220VAC 60Hz | 500 | 1700 | 280 | IP55,NEMA 4, NEMA 4X | 500 | 120 | R134a | 56 | |
220VAC 60Hz | 1000 | 3400 | 430 | IP55,NEMA 4, NEMA 4X | 1000 | 230 | R134a | 62 | |
220VAC 60Hz | 1200 | 4080 | 498 | IP55,NEMA 4, NEMA 4X | 1000 | 240 | R134a | 62 | |
220VAC 60Hz | 1300 | 4440 | 532 | IP55,NEMA 4, NEMA 4X | 1000 | 260 | R134a | 63 | |
220VAC 60Hz | 1500 | 5100 | 600 | IP55,NEMA 4, NEMA 4X | 1000 | 300 | R134a | 63 | |
220VAC 60Hz | 2000 | 6800 | 745 | IP55,NEMA 4, NEMA 4X | 1000 | 500 | R134a | 63 | |
220VAC 60Hz | 2500 | 8500 | 846 | IP55,NEMA 4, NEMA 4X | 2000 | 560 | R134a | 63 | |
220VAC 60Hz | 3000 | 10200 | 1240 | IP55,NEMA 4, NEMA 4X | 2000 | 720 | R134a | 63 | |
220VAC 60Hz | 3500 | 11900 | 1360 | IP55,NEMA 4, NEMA 4X | 2000 | 1250 | R134a | 63 |
Model | Voltage | Nominal cooling capacity(W) (L35/L35) | Nominal cooling capacity(Btu/hr) (L35/L35) | Power consumption(W)(L35/L35) | IP Grade | Heater (W)(option) | Internal air flow (m3/h) | Refrigerant | Noise (dbA) |
110VAC 60Hz | 300 | 1020 | 170 | IP55,NEMA 4, NEMA 4X | 500 | 100 | R134a | 56 | |
110VAC 60Hz | 400 | 1360 | 215 | IP55,NEMA 4, NEMA 4X | 500 | 110 | R134a | 56 | |
110VAC 60Hz | 500 | 1700 | 280 | IP55,NEMA 4, NEMA 4X | 500 | 120 | R134a | 56 | |
110VAC 60Hz | 1000 | 3400 | 430 | IP55,NEMA 4, NEMA 4X | 1000 | 230 | R134a | 62 | |
110VAC 60Hz | 1200 | 4080 | 498 | IP55,NEMA 4, NEMA 4X | 1000 | 240 | R134a | 62 | |
110VAC 60Hz | 1300 | 4440 | 532 | IP55,NEMA 4, NEMA 4X | 1000 | 260 | R134a | 63 | |
110VAC 60Hz | 1500 | 5100 | 600 | IP55,NEMA 4, NEMA 4X | 1000 | 300 | R134a | 63 |
to be continued ,please contact with your sales expert.
Name | Specification |
| |
| |
| |
| |
|
Advantages&Why?
Whether in industrial plants or outdoor telecom sites, our AC units maintain stable temperatures, safeguarding critical electronics.
Prevents overheating, condensation, and equipment downtime with a trusted, high-performance cooling system.
Reduce operational costs without compromising on reliability, thanks to smart design and low energy consumption.
Decades years of experience
Global supply capability
Customized cooling solutions
Fast delivery and technical support
Widely used in telecom, utilities, transportation, and energy storage industries
Cooling capacity ranges from 300w to 5000w
Voltage range :AC220V 50HZ,AC220V 60HZ,60HZ , AC110V60HZ ,DC48V
Widely used for outdoor telecom cabinets ,battery cabinets,elecric cabinets and industry control cabinets etc.
Remote monitoring system supported, communication protocol is RS485

Our engineering team can recommend the right model based on:
Cabinet size
Heat load
Installation method
Environment
Voltage requirements
Contact us for datasheets, drawings, pricing, or OEM/ODM solutions.